Art. No. SC 1000 KNX
Activation of the
setpoint temperature
limit in cooling operation
via object
No
Yes
A setpoint limit enabled in the ETS can
be activated or deactivated as
necessary using a 1-bit object. For this,
this parameter can be set to "Yes". In
this case, the controller only takes the
setpoint limit into account, if it has been
enabled via the object "Cooling setpoint
temp. limit" ("1" telegram). If the
limitation is not enabled ("0" telegram),
the cooling setpoint temperatures are
not limited.
This parameter is visible only if setpoint
temperature monitoring is enabled.
Difference to outdoor
temperature in cooling
operation
1 K...6 K...15 K This parameter defines the maximum
difference between the setpoint
temperature in Comfort mode and the
outdoor temperature with an active
setpoint temperature limit.
This parameter is visible only if setpoint
temperature monitoring is enabled.
However, this is only if the parameter
"Setpoint temperature limit in cooling
operation" is then set to "Only difference
to outdoor temperature" or "Max.
setpoint temperature and difference to
outdoor temperature".
Max. setpoint
temperature in cooling
operation
20°C...26°C...35°C This parameter defines the maximum
setpoint temperature in Comfort mode
with an active setpoint temperature limit.
This parameter is visible only if setpoint
temperature monitoring is enabled.
However, this is only if the parameter
"Setpoint temperature limit in cooling
operation" is then set to "Only max.
setpoint temperature" or "Max. setpoint
temperature and difference to outdoor
temperature".
h Room temperature control (RTC) -> Controller functionality
Presence detection none
Presence button
Motion detector
In the "None" setting, the presence
mode is deactivated.
In the "Presence button" setting,
presence detection takes place using a
button on the device or via the presence
object (e.g. other push button sensors).
When the presence button is pressed
from the night mode or frost/heat
protection, the comfort extension is
activated. If the presence button is
pressing in standby mode, the controller
activates the comfort mode for the
duration of the presence mode.
In the "Motion detector" setting,
presence detection takes place using an
external motion detector, coupled to the
presence object. Comfort mode is
recalled when a presence is detected.
Page 303 of 347
Software "Smart Control 501511"
Parameters

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Jung Smart Control SC 1000 KNX and is the answer not in the manual?

Jung Smart Control SC 1000 KNX Specifications

General IconGeneral
BrandJung
ModelSmart Control SC 1000 KNX
CategoryController
LanguageEnglish

Related product manuals