Art. No. SC 1000 KNX
Calibration of received
temperature value
(-128...127) * 0.1 K
-128...0...127 Determines the value by which the
temperature value received from the bus
is calibrated.
This parameter is only visible when the
temperature recording system requires
that a temperature value is received.
Request time for
received temperature
value
(0...255) * 1 min;
0 = inactive
0...255 The request time for the temperature
value received from the bus is specified
here. In the "0" setting, the temperature
value is not automatically polled by the
controller. In this case the
communication partner must transmit its
temperature value itself.
This parameter is only visible when the
temperature recording system requires
that a temperature value is received.
Transmission when
room temperature
change by
(0...255) * 0.1 K; 0 =
inactive
0...3...255 Determines the size of the value change
of the room temperature after which the
current values are automatically
transmitted on the bus via the "Actual
temperature" object.
Cyclical transmission of
room temperature
(0...255) * 1 min; 0 =
inactive
0...15...255 This parameter specifies whether and
when the determined room temperature
is to be periodically output via the
"Actual temperature" object.
Page 310 of 347
Software "Smart Control 501511"
Parameters

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Jung Smart Control SC 1000 KNX and is the answer not in the manual?

Jung Smart Control SC 1000 KNX Specifications

General IconGeneral
BrandJung
ModelSmart Control SC 1000 KNX
CategoryController
LanguageEnglish

Related product manuals