Art. No. SC 1000 KNX
bus after a scene recall or during
storage of a scene.
Visible only if "Full-surface operation =
enabled"!
The following parameters are only visible for the rocker function "Venetian Blind"...
Command on pressing
rocker
Rocker X.1:UP /
Rocker X.2: DOWN
Rocker X.1:DOWN /
Rocker X.2: UP
Rocker X.1:TOGGLE /
Rocker X.2: TOGGLE
This parameter defines the running
direction of a drive after a button-press.
If the setting is "TOGGLE", the direction
is changed after each long time
command. If several push buttons are to
control the same drive, the long time
objects of the push buttons must be
interlinked for a correct change of the
running direction.
Operation concept short – long – short
long – short
short – long
long – short or short
For Venetian blind control, four different
operation concepts can be selected. For
these concepts, the ETS shows further
parameters.
Time between short-
time and long-time
command
Rocker 1.1
(1...3000 x 100 ms)
1...4...3000 This parameter sets the time after which
the long time operation will be evaluated
on pressing the top (or left-hand) button
of the rocker. This parameter is not
visible with "Operation concept = long –
short"!
Time between short-
time and long-time
command
Rocker 1.2
(1...3000 x 100 ms)
1...4...3000 This parameter sets the time after which
the long time operation will be evaluated
on pressing the bottom (or right-hand)
button of the rocker. This parameter is
not visible with "Operation concept =
long – short"!
Slat adjusting time
rocker 1.1
(0…3000 x 100 ms)
0...5...3000 Time during which a transmitted long
time telegram can be terminated by
releasing the top (or left-hand) button of
the rocker (short time). This function
serves to adjust the slats of a blind. This
parameter is not visible with "Operation
concept = long – short"!
Slat adjusting time,
rocker 1.2
(0…3000 x 100 ms)
0...5...3000 Time during which a transmitted long
time telegram can be terminated by
releasing the bottom (or right-hand)
button of the rocker (short time). This
function serves to adjust the slats of a
blind. This parameter is not visible with
Page 315 of 347
Software "Smart Control 501511"
Parameters