Art. No. SC 1000 KNX
Function: Command value
Object
h
99
Function
Cmd. value, add. cooling
(PWM)
Name
C.Output
Type
1-bit
DPT
1.001
Flag
C, -, T, (R)
1
Description 1-bit object to output the continuous PWM command value for additional
cooling in two-level operation. This object is only available in this way if the
type of feedback control is configured to "Switching PI control (PWM)".
Function: Command value
Object
h
99
Function
Cmd. value, additional
cooling
Name
C.Output
Type
1-bit
DPT
1.001
Flag
C, -, T, (R)
1
Description 1-byte object to output the switching command value for additional cooling in
two-level operation. This object is only available in this way if the type of
feedback control is configured to "Switching 2-point feedback control".
Object for additional PWM heating command value output and combined valve PWM
additional heating/cooling
Function: Command value
Object
h
100
Function
PWM command value for
heating / PWM command
value, basic heating
Name
C.Output
Type
1 byte
DPT
5.001
Flag
C, -, T, (R)
1
Description 1-byte object to output the internal continuous command value of a PWM
controller of the heating mode. In two-level heating mode, command value
output for the basic heating. This object is only available in this way if the type
of feedback control is configured to "Switching PI control (PWM)". In addition
to the switching 1 bit command value of the PWM, the calculated continuous
command value of the controller can also be transmitted to the bus and
displayed, e.g. in a visualisation.
Function: Command value
Object
h
100
Function
PWM command value for
heating/cooling / PWM
command value, basic level
Name
C.Output
Type
1 byte
DPT
5.001
Flag
C, -, T, (R)
1
Description 1-byte object to output the combined continuous command value of a PWM
controller of the heating and cooling mode. In two-level heating/cooling mode,
command value output for the basic level This object is only available in this
way if the command values for heating and cooling mode are output to a
shared object (parameter-dependent). The type of feedback control must also
be configured to "Switching PI control (PWM)". In addition to the switching 1
bit command value of the PWM, the calculated continuous command value of
the controller can also be transmitted to the bus and displayed, e.g. in a
visualisation.
1: For reading, the R-flag must be set. The last value written to the object via the bus or by the
device will be read.
Page 42 of 347
Software "Smart Control 501511"