EasyManua.ls Logo

Jung Smart Control SC 1000 KNX - Page 93

Jung Smart Control SC 1000 KNX
347 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Art. No. SC 1000 KNX
i The objects "D.Input channel x Venetian blind feedb. Blind/shutter height and "D.Input
channel x Venetian blind feedb. Slat pos." interpret values to be sent or received on the
basis of the KNX data point type 5.001 (Scaling). The decimal data values 0...255 are
evaluated as percentages 0...100 % and displayed in the device display.
i Since Venetian blind or shutter actuators normally transmit position values as feedback, the
activated motors stop when driver runs have been completed. For this reason, status
indications of the channel element concerned do not normally change during a press of the
sensor surface, but only when the buttons are released and the drive runs are stopped. By
contrast, a displayed status value can already change even during an operation if the drive
is already in the end position or cannot pass through the entire position range due to
disabling functions.
Page 93 of 347
Software "Smart Control 501511"
Functional description

Table of Contents

Related product manuals