Art. No. SC 1000 KNX
i The objects "D.Input channel x Venetian blind feedb. Blind/shutter height and "D.Input
channel x Venetian blind feedb. Slat pos." interpret values to be sent or received on the
basis of the KNX data point type 5.001 (Scaling). The decimal data values 0...255 are
evaluated as percentages 0...100 % and displayed in the device display.
i Since Venetian blind or shutter actuators normally transmit position values as feedback, the
activated motors stop when driver runs have been completed. For this reason, status
indications of the channel element concerned do not normally change during a press of the
sensor surface, but only when the buttons are released and the drive runs are stopped. By
contrast, a displayed status value can already change even during an operation if the drive
is already in the end position or cannot pass through the entire position range due to
disabling functions.