ACX7348 Grounding Cable and Lug Specicaons
For installaons that require a separate grounding conductor to the chassis, you must ground the router
before you connect power. Grounding the router ensures proper operaon and meets safety and
electromagnec interference (EMI) requirements. To ground an ACX7348 router, connect a grounding
cable to earth ground, and then aach the grounding cable to the chassis grounding point.
WARNING: To comply with GR-1089 requirements, all intra-building copper cabling
used for transceiver ports must be shielded and grounded at both ends.
CAUTION: Before router installaon begins, have a licensed electrician aach a cable
lug to the grounding cables that you supply. A cable with an incorrectly aached lug can
damage the router.
NOTE: You must ensure that all cables are rated for the environment in which they are deployed.
For an ACX7348 router, you need a grounding cable and an LCD6-14A-L lug (see Figure 20 on page
46. The grounding lug accommodates a 6 AWG , 90° C stranded copper wire (green with yellow
insulaon), or as required by the local code.
Figure 20: Grounding Cable Lug Specicaons