Table 20: Rack Requirements for ACX7348 Routers
(Connued)
Rack Requirement Guidelines
Rack size and
strength
Ensure that the rack complies with the standards for a 19-in. rack as dened in
Cabinets,
Racks, Panels, and Associated Equipment
(document number EIA-310–D), published by
the Electronics Industry Associaon.
Use an 800-mm rack as dened in the four-part
Equipment Engineering (EE) European
telecommunicaons standard for equipment pracce
(document numbers ETS 300
119-1 through 119-4), published by the European Telecommunicaons Standards
Instute (hp://www.etsi.org).
Ensure that the rack rails are spaced widely enough to accommodate the external
dimensions of the router chassis. The outer edges of the front-mounng brackets
extend the width to 19 in. (48.26 cm).
Ensure that the spacing of rails and adjacent racks allows for proper clearance around
the router and rack.
Rack connecon
to building
structure
Secure the rack to the building structure.
If earthquakes are a possibility in your geographical area, secure the rack to the oor.
Secure the rack to the ceiling brackets and to the wall or oor brackets for maximum
stability.
Cabinet Requirements for ACX7348 Routers
You can mount an ACX7348 router in an enclosure or cabinet that contains a two-post or four-post 19-
in. open rack as dened in
Cabinets, Racks, Panels, and Associated Equipment
(document number
EIA-310-D), published by the Electronics Industry Associaon.
Table 21 on page 50 provides the cabinet requirements and guidelines for an ACX7348 router.