ACX7348 Rack and Cabinet Requirements
SUMMARY
You must install the ACX7348 router on a rack or in
a cabinet that meets specic dimension, strength,
and airow requirements.
IN THIS SECTION
Rack Requirements for ACX7348
Routers | 48
Cabinet Requirements for ACX7348
Routers | 49
Rack Requirements for ACX7348 Routers
You can mount the ACX7348 routers on two-post racks or four-post racks.
The size, strength, and locaon of the rack must accommodate the router's weight and external
dimensions.
Table 20 on page 48 provides the rack requirements and guidelines for ACX7348 routers.
Table 20: Rack Requirements for ACX7348 Routers
Rack Requirement Guidelines
Rack type Use a two-post or four-post rack that provides bracket holes or hole paerns spaced at 1 U
increments (1.75 in. or 4.45 cm), and ensure that the rack meets the size and strength
requirements to support the weight of the router.
A U is the standard rack unit dened in
Cabinets, Racks, Panels, and Associated Equipment
(document number EIA-310–D) published by the Electronics Industry Associaon.
Mounng bracket
hole spacing
Ensure that the holes in the mounng brackets are spaced at 1 U (1.75 in. or 4.45 cm) so
that the router can be mounted in any rack that provides holes spaced at that distance.