For service personnel to remove and install hardware components, there must be adequate space at the
front and back of the services gateway. At least 24 in. (61 cm) is required both in front of and behind
the services gateway. NEBS GR-63 recommends that you allow at least 30 in. (76 cm) in front of the
rack and 24 in. (61 cm) behind the rack.
Figure 35: Clearance Requirements
g036006
65 cm
Front: 76 cm clearance required for maintenance
44 cm
Minimum
13 cm between
chassis and wall
or non-heat-
producing
surface;
Minimum
15.2 cm
between
devices
Sides:
Rear: 61 cm clearance required
for maintenance
RELATED DOCUMENTATION
SRX3600 Services Gateway Rack Size and Strength Requirements | 67
Connecting the SRX3600 Services Gateway to the Building Structure | 69
SRX3600 Services Gateway Spacing of Mounting Bracket Holes | 69