Operating instructions
No.
1601
1602
1603
Description
Test opening with emergency ope-
ning rubber cable not successful
during the setting-up procedure.
Excessivetensionofemergency
opening rubber cable (operation).
Excessivetensionofemergency
opening rubber cable (setting-up).
Corrective action
Check the emergency opening rubber cable, check
respectively make sure that the sliding wings can
be easily moved.
Without D-BEDIX the door remains open.
Reduce the tension.
Reduce the tension.
Fatal error (door remains open).
Mode
NIGHT
Closure
possible
yes
yes
yes
No.
2000
Description
More than 5 successive
obstructions.
Corrective action
Remove the obstacle.
Mode
NIGHT
Closure
possible
yes
No.
1000
1001
1002
1007
Description
Reset has been triggered (purely
informative message).
• Minimumopeningwidthhasnot
been reached during setting-up.
• Nomassmeasurement.
• NoResetcarriedoutafterDIP1
changing.
Reset not possible in battery-
operated mode.
A sliding wing weight of <20 kg was
measured.
Corrective action
-
Remove the obstacle, check/restore the free
running movement of the sliding wings, check the
locking, carry out a Reset.
Plug in the mains connector.
Check the sliding wing and the toothed belt cou-
pling.
Mode
NIGHT
Closure
possible
-
no
no
yes