• Theemergencybatteryissuppliedinchargedcondition.
• Ifitisregularlyused,itslifetimeisapproximately5years.
• Theemergencybatterycanberechargedapproximately1‘200times(dependingonthe
respective depth of the discharge).
• Ifanindividualbatteryneedstobereplaced,itisimportanttocheckpreviouslyifthe
new battery has a minimum voltage of 12,4 VDC (not under load). Should this require-
mentnotbefullled,itmustberechargedbeforebeingused.
Attention:
Batteries of different brands (manufacturers) must never be used together!
Recharging
1. Disconnect the connection cable from the batteries.
2. Rechargethebatteriesindividuallyduringapproximately12hours:
Charging voltage 14,7 VDC
Chargingcurrentmax. 0,36 A
3. Reconnect the connection cable and mark the charging date.
• Neverstoretheemergencybatteryindischargedcondition(rechargeitassoonaspos-
sible).
• Beforestoringtheemergencydisconnectalltheconsumers.
• Neverexposeittoaheatsource.
• Neverexposeittodirectinsolation.
• Storethebatteryinverticalposition,onahorizontalbase.
• Checkthevoltageatregularintervals.
• Usenothingbutadryragforcleaningthebattery.
Attention:
If the storage temperatures are below freezing point, the battery must be
handled with great care, as the synthetic material of the battery housing
hardens and thus more sensitive to damaging.
• Storeinacoolanddryplace.
• Ambienttemperaturebetween-35°Cand+50°C.
• Thestoragetemperaturehasaninuenceonthespontaneousdischargeoftheemer-
gency battery:
Storage temperature Storage intervals
below 20 °C every 9 months
20...30 °C every 6 months
30...40 °C every 3 months
above 40 °C reduction of the lifetime