EasyManua.ls Logo

Kamstrup MULTICAL 401 - Data;pulse inputs (66-0 R); M-Bus, EN 1434, EN 13757;pulse inputs (66-0 P)

Kamstrup MULTICAL 401
75 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TECHNICAL DESCRIPTION MULTICAL
®
401
5512-091 GB/02.2008/Rev. J1
49
11.2 Data/pulse inputs (66-0R)
Figure 38 Figure 39
The data connection in this module is identical with that described earlier.
Two extra pulse signals, e.g. from cold-water and hot-water meters, can also be connected to the meter. Meters
with both Reed switch and transistor output can be connected. The inputs have a max. input frequency of
0.5
Hz.
Reed switches with built-in protective resistances of up to 1 kOhm can be used and both Input A and Input B
contains the necessary de-bouncing for Reed switches.
No Darlington transistors should be used when connecting the transistor outputs to Input A and Input B, as the
voltage level at logical”0” must be
0.5 V. In addition, the leak current in the output must be less than 1 A.
The pulse inputs can be configured for most cold-water and hot-water meters.
See section 3.3.3
>FF< Input a, >GG< Input b for information on configuration of pulse values and maximum
flowrate. Required configuration must be stated when ordering. Reconfiguration can be done by the use of the PC-
program METERTOOL.
11.3 M-Bus, EN 1434, EN 13757/pulse inputs (66-0P)
M-Bus, EN 1434/pulse inputs (66-0S)
Figure 40 Figure 41
The M-Bus modules are used for remote reading of MULTICAL
®
401 via an M-Bus net work.
To make an M-Bus system work, it is necessary to give each M-Bus module a unique address. The M-Bus address
is automatically generated based on the customer meter number, and can easily be changed either by means of
the hand-held terminal MULTITERM or by means of the PC program of METERTOOL.

Table of Contents

Related product manuals