EasyManuals Logo

KEB combivert R6-S Applications Manual

KEB combivert R6-S
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #126 background imageLoading...
Page #126 background image
Page 3.9 - 6 COMBIVERT R6-S © KEB, 2008-02
Dene CP-Parameters
3.9.3 Example
Anusermenuwiththefollowingfeaturesshallbeprogrammedasexample:
1. Display of the actual line frequency (ru.03) in the respective set
2. Setting of a comparison level (LE.00) in set 2
3. Setting of a comparison level (LE.00) in set 3
1.) ud.15 = 1 ; CP.01
ud.16 = 0203h ; Parameter address for ru.03
ud.17 = 256 ; Display in the active set
2.) ud.15 = 2 ; CP.02
ud.16 = 0D00h ; Parameter address for LE.00
ud.17 = 4 ; Setting in set 2
3.) ud.15 = 3 ; CP.03
ud.16 = 0D00h ; Parameter address for LE.00
ud.17 = 8 ; Setting in set 3
4.) ud.15 = 4 ; CP.04
ud.16 = -1: off ; CP.04 is faded out
ud.17 = xxx ; ud.17 is without function
Set all other parameters like CP.4 to "off", that there is no display.
The acceptance of values occurs only after power-on reset of the operator.

Table of Contents

Other manuals for KEB combivert R6-S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB combivert R6-S and is the answer not in the manual?

KEB combivert R6-S Specifications

General IconGeneral
BrandKEB
Modelcombivert R6-S
CategoryPower Supply
LanguageEnglish

Related product manuals