Operating and appliance data
© KEB, 2008-02 COMBIVERT R6-S Page 3.2 - 7
3
10
Parameter Addr. R PG E Min. value Max. value Res. [?] Default
ru.20
DC output voltage / peak
value
0214h rw - - 0 778 1 V -
Parameter ru.20 enables to recognize voltage peaks within an operating cycle. For that the highest value
of ru.19 is stored in ru.20. The peak value memory can be cleared by pressing the UP, or DOWN key or via
bus by writing any value you like to the address of ru.20. Switching off COMBIVERT R6-S also clears the
memory.
Parameter Addr. R PG E Min. value Max. value Res. [?] Default
ru.21 Input terminal state 0215h ro - - 0 4095 1 - -
Display of the digital inputs set currently. The logic levels are indicated at the input terminals or at the inter-
nal inputs regardless of the following logic operations (see chapter 3.3 „Digital inputs“). According to follow-
ingtableaspecicdecimalvalueisgivenoutforeachdigital input. If several inputs are controlled, the sum
of the decimal values is indicated.
Bit Decimal value Input Terminal
0 1 ST (prog. input „control release/reset“) X2A.12
1 2 RST (prog. input „reset“) no
2 4 F (prog. input) no
3 8 R (prog. input) no
4 16 I1 (prog. input 1) X2A.13
5 32 I2 prog. input 2) X2A.14
6 64 I3 (prog. input 3) X2A.15
7 128 I4 (prog. input 4) X2A.16
8 256 IA (internal input A) no
9 512 IB (internal input B) no
10 1024 IC (internal input C) no
11 2048 ID (internal input D) no
Parameter Addr. R PG E Min. value Max. value Res. [?] Default
ru.22 Internal input state 0216h ro - - 0 4095 1 - -
Display of the digital external and internal inputs set currently. The input is only regarded as set if it is available
as effective signal to the further processing (i.e. accepted through strobe, edge-triggering or logic operation).
According to table like ru.21aspecicdecimalvalueisoutput for each digital input. If several inputs are con-
trolled, the sum of the decimal values (see ru.21) is indicated (also see chapt. 3.4 „Digital inputs“).

Table of Contents

Other manuals for KEB combivert R6-S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB combivert R6-S and is the answer not in the manual?

KEB combivert R6-S Specifications

General IconGeneral
BrandKEB
Modelcombivert R6-S
CategoryPower Supply
LanguageEnglish

Related product manuals