Syntax Rules
6 Keysight 3458A Quick Reference Guide
6 Keysight 3458A Quick Reference Guide
Syntax Rules
– Command headers may be entered in upper 
or lower case.
– Parameters may be entered in upper case, 
lower case, or as a numeric value. Numeric 
values can be either integer, floating-point, or 
exponential in format. Parameters in 
floating-point format are rounded to the 
nearest integer if the command requires an 
integer. For example, “SUB 2.49” is rounded 
down to “SUB 2" and “SUB 2.5” is rounded up 
to “SUB 3”.
– Command headers and parameters must be 
separated by either a space or a comma.
– You can default a parameter by omitting it or 
replacing it with -1 (minus 1). From remote 
only, you can use two commas to indicate a 
default value.
– The carriage return (cr), line feed (lf), 
semicolon (;), or EOI sent concurrent with the 
last character indicate the end of message 
(command terminator) to the multimeter. 
When you send a command from the system 
controller in the standard format (e.g. 
OUTPUT 722:“TEST”), the controller typically 
adds a cr lf to the end of the command. With 
its input buffer off (off is the power-on input 
buffer mode), the multimeter processes the cr 
immediately, but does not process the lf until 
the command completes execution. This 
means that, because of the lf, the bus is held 
and you cannot regain use of the controller 
until the multimeter is done executing the