75
Table 3 Technical parameters EVO-T+3000
PARAMETRY EVO-T + 3000 CPR EVO-T + 3000 RR
Nominal air ow rate [m
3
/h] static pressure at External 300/ 150Pa 300/95 Pa
Unit dimensions
L
[mm]
1300 1200
L1 639 589
B 612
B1 648
H 355 400
H1 395 445
Net weight [kg] / Gross weight with pallet 95 / 125 75 / 110
Flexible duct connections [mm] 265 x 290 265 x 335
Power supply voltage: 230 V; 50 Hz
Heat exchanger counterow rotary
Heat exchanger eciency* 91% 80%
Exchanger motor
Power
N/A
25 W
Voltage 230 V; 50 Hz
Absorbed current 0,23 A
Air temperature -25 do 50°C
Fans
Power 2×83 W
Voltage 230 V; 50 Hz
Absorbed current 2×0,75 A
Air temperature -25 do 50°C
Sound power level
To room at capacity
30% 35 dB(A) 35 dB(A)
100% 50 dB(A) 50 dB(A)
Into duct at air ow
30% 57dB / 50dB(A) 57dB / 50dB(A)
100% 66dB / 60dB(A) 66dB / 60dB(A)
Control system Digital controller
Exhaust and outlet air lter according to EN 779 / according to EN ISO 16890
G4/Coarse 80% – standard
M5 / ePM
10
50% – option
F7 / ePM
1
60% – option for air supply
EH heater on supply air inlet after heat recovery exchanger (option WH/EH) 1200 W
*Note: Data provided by manufacturers of counterow plate heat exchangers, according to the EN 308 and EUROVENT