EasyManua.ls Logo

Lakeshore 336 - Polarity and Monitor out Scaling Parameters

Lakeshore 336
192 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.6.1 Monitor Units 79
| www.lakeshore.com
5.6.1.1 Polarity and Monitor Out Scaling Parameters
In the Monitor Out and Open Loop modes, the unpowered analog outputs can be con-
figured as either unipolar (0 V to +10 V) or bipolar (–10 V to +10 V) outputs. In bipolar
mode, the Monitor Out –10 V setting determines the temperature or sensor value at
which the output should be –10 V. In unipolar mode, the Monitor Out 0 V setting
determines the temperature or sensor value at which the output should be 0 V. The
Monitor Out +10 V setting determines the temperature or sensor value at which the
output should be +10 V in either unipolar or bipolar modes.
For example, if Polarity is set to Bipolar, then setting the Monitor Out –10 V parameter
to 0 K and the Monitor Out +10 V parameter to 100 K will cause the analog output to
correspond to the input temperature as shown in FIGURE 5-3. In this case if the actual
reading was 50 K, then the output would be at 0 V (middle of the scale).
If we set the Polarity parameter to Unipolar, the output would be as shown in
FIGURE 5-4. In this case if the actual reading was 50 K, the analog output would be
+5 V (middle of the scale).
Menu Navigation:
Output SetupQOutput (3 or 4)QPolarityQ(Unipolar or Bipolar)
Output SetupQOutput (3 or 4)QMonitor Out –10 VQ(See note below)
Output SetupQOutput (3 or 4)QMonitor Out 0 VQ(See note below)
Output SetupQ Output (3 or 4)QMonitor Out +10 VQ(See note below)
Monitor Out -10 V, 0 V, and +10 V settings depend on the Monitor Units selected, and are
limited to the acceptable values of the selected units.
Default: PolarityQUnipolar
Monitor Out -10 VQ0.0000 K
Monitor Out 0 VQ0.0000 K
Monitor Out +10 VQ1000 K
Interface Command: ANALOG
FIGURE 5-2 Unipolar and bipolar mode
FIGURE 5-3 Analog output with polarity set to bipolar
FIGURE 5-4 Output with polarity parameter set to unipolar
Bipolar
Lowest Middle Highest
–10 V 0 V +10 V
0 V +5 V +10 V
Lowest Middle Highest
Input mode
Input
Output
Input
Output
Unipolar
Bipolar
0 K 50 K 100 K
–10 V 0 V +10 V
Input
Output
0 V +5 V +10 V
0 K 50 K 100 K
Input
Output
Unipolar

Table of Contents

Related product manuals