Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05 270
10 Parameter reference
10.2 Parameter list | C00352
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00352
C00353
C00354
Parameter | Name:
C00352 | CAN Slave/Master
Data type: UNSIGNED_8
Index: 24223
d
= 5E9F
h
The drive starts as CAN master after mains switching if the value "1" has been entered and saved here.
System bus "CAN on board"
Selection list (Lenze setting printed in bold)
0Slave
1Master
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00353 | CAN IN/OUT COBID source
Data type: UNSIGNED_8
Index: 24222
d
= 5E9E
h
Identifier allocation procedure for the CANx In/OUT process data
System bus "CAN on board"
Selection list Info
0 COBID = C0350 + LenzeBaseID COBID = device address + LenzeBaseID
1 COBID = C0350 + CANBaseID COBID = device address + CANBaseID (C00354/x
)
2 COBID = C0354/x COBID = C00354/x
+ 384
Subcodes Lenze setting Info
C00353/1 1: COBID = C0350 + CANBaseID COBID source CAN1_IN/OUT
C00353/2 1: COBID = C0350 + CANBaseID COBID source CAN2_IN/OUT
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00354 | COBID
Data type: UNSIGNED_32
Index: 24221
d
= 5E9D
h
Setting of the default COBID according to CANopen
• A change of the COBID will only become effective after a CAN reset node.
System bus "CAN on board"
Setting range (min. hex value | max. hex value)
0x00000000 0xFFFFFFFF
Value is bit-coded: Info
Bit 0 COBID Bit0 • Bit 0 ... 10: COB-ID
• Bit 11 ... 30: Reserved
• Bit 31: PDO invalid (is not transmitted)
... ...
Bit 31 PDO invalid
Subcodes Lenze setting Info
C00354/1 513 COBID CAN1_IN
C00354/2 385 COBID CAN1_OUT
C00354/3 769 COBID CAN2_IN
C00354/4 641 COBID CAN2_OUT
Read access Write access CINH PLC STOP No transfer COM MOT