3 Commissioning
3.4 Commissioning with the »Engineer«
36
Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4. Adapt parameters of the application:
Tip!
•Via the Signal flow button, you get one dialog level lower to the signal flow of the appli-
cation with further parameterisation opportunities. See chapter entitled
"Parameterisation dialog
". ( 122)
The preconfigured I/O connection in the selected control mode can be changed via con-
figuration parameters. See chapter entitled "User-defined terminal assignment
". ( 114)
More detailed information on the drive application:
Drive application
( 121)
Interface description
( 127)
Setting parameters (short overview)
( 132)
Pre-assignment of the drive application
( 133)
Terminal assignment of the control modes
( 139)
Parameter Lenze setting Info
Value Unit
Accel. time - main setpoint
(C012
)
2.0 s The setpoint is led via a ramp function generator with li-
near characteristic. The ramp function generator con-
verts setpoint step-changes at the input into a ramp.
L_NSet_1
( 309)
Decel. time - main setpoint
(C013
)
2.0 s
Reference speed
(C011
)
1500 rpm All speed setpoint selections are provided in % and al-
ways refer to the reference speed set in C011
.
The motor reference speed is given on the motor name-
plate.
Deceleration time - quick
stop
(C105
)
5.0 s When "quick stop" is requested, the motor control is de-
coupled from the setpoint selection and within the de-
celeration time parameterised in C105
, the motor is
brought to a standstill in (n
act
=0).
Activate/Deactivate quick stop
( 50)
Fixed setpoint 1
(C039/1
)
40.0 % A fixed setpoint for the setpoint generator can be acti-
vated instead of the main setpoint via the digital inputs
DI1 and DI2.
The fixed setpoints are selected in [%] based on the
reference speed (C011
).
L_NSet_1
( 309)
Fixed setpoint 2
(C039/2
)
60.0 %
Fixed setpoint 3
(C039/3
)
80.0 %