EasyManua.ls Logo

Lenze 9325 - Mains Disconnection; Insulation; Replacement of Defective Fuses

Lenze 9325
524 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
4-10
SHB9300CRV EN 2.0
4.2.1.2 Insulation
The controllers have an insulation (isolating distance)between the power terminals and the control
terminals as well as to the housing:
l
Terminals X1 and X5 have a double basic isolation (double insulating distance, safe mains
isolation to VDE0160, EN50178). The protection against contact is ensured without any
further measures.
l
The control inputs and outputs of all controllers are electrically isolated.
Danger!
l
Terminals X3, X4, X6, X7, X8, X9, X10 have a single basic isolation (single insulating
distance).
l
Protection against contact in the event of fault is ensured only by additional measures.
l
If an external voltage supply (24V DC) is used, the insulation level of the controller depends
on the insulation level of the voltage source.
reinforced insulation
single basic insulation
Fig. 4-6 Basic insulation in the controller
4.2.1.3 Replacement of defective fuses
Replace defective fuses with the prescribed type only when no voltage is applied. (
&
3-6)
l
For single drives, the controller carries a hazardous voltage up to three minutes after mains
disconnection.
l
In a drive network, all controllers must be inhibited and disconnected from the mains.
4.2.1.4 Mains disconnection
Make a safety disconnection between the controller and the mains only via a contactor at the input
side.
l
Please note that in a drive network all controllers must be inhibited.
Show/Hide Bookmarks

Table of Contents

Related product manuals