4.2.1.2 Fusing and terminal data
Fuse data
Inverter I51AE125B
I51AE137B
I51AE125D
I51AE137D
I51AE155B
I51AE175B
I51AE155D
I51AE175D
Cable installaon in compliance with EN 60204-1
Installaon method B2
operaon without mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 10 10 16 16
Circuit breaker
Characteriscs B
Max. rated current A 10 10 16 16
operaon with mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 10 10 16 16
Circuit breaker
Characteriscs B
Max. rated current A 10 10 16 16
Earth-leakage circuit breaker
1-phase mains connecon ≥ 30 mA, type A or B
3-phase mains connecon - ≥ 30 mA, type B - ≥ 30 mA, type B
Fuse data
Inverter I51AE211B
I51AE215B
I51AE222B
I51AE211D
I51AE215D
I51AE222D
Cable installaon in compliance with EN 60204-1
Installaon method B2
operaon without mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 25 25
Circuit breaker
Characteriscs B
Max. rated current A 25 25
operaon with mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 25 25
Circuit breaker
Characteriscs B
Max. rated current A 25 25
Earth-leakage circuit breaker
1-phase mains connecon ≥ 30 mA, type A or B
3-phase mains connecon - ≥ 30 mA, type B
Electrical installaon
Mains connecon
1-phase mains connecon 230/240 V