14.3 3-phase mains connecon 230/240 V
14.3.1 Rated data
The output currents apply to these operang condions:
At a switching frequency of 2 kHz or 4 kHz: Max. ambient temperature 45°C.
At a switching frequency of 8 kHz or 16 kHz: Max. ambient temperature 40 °C.
Inverter I51AE125D I51AE137D I51AE155D I51AE175D I51AE211D I51AE215D I51AE222D
Rated power kW 0.25 0.37 0.55 0.75 1.1 1.5 2.2
Rated power hp 0.33 0.5 0.75 1 1.5 2 3
Mains voltage range 3/PE AC 170 V ... 264 V, 45 Hz ... 65 Hz
Output voltage 3 AC 0 V … 230 V/240 V
Rated mains current
without mains choke A 2.6 3.9 4.8 6.4 7.8 9.5 13.6
with mains choke A 2 3 3.8 5.1 5.6 6.8 9.8
Apparent output power kVA 0.6 0.9 1.2 1.6 2.2 2.6 3.6
Output current
2 kHz A - - 3.2 4.2 6 7 9.6
4 kHz A 1.7 2.4 3.2 4.2 6 7 9.6
8 kHz A 1.7 2.4 3.2 4.2 6 7 9.6
16 kHz A 1.1 1.6 2.1 2.8 4 4.7 6.4
Weight kg 0.75 0.95 1.35
Weight lb 1.7 2.1 3
14.4 3-phase mains connecon 400 V
14.4.1 Rated data
The output currents apply to these operang condions:
At a switching frequency of 2 kHz or 4 kHz: Max. ambient temperature 45°C.
At a switching frequency of 8 kHz or 16 kHz: Max. ambient temperature 40 °C.
Inverter I51AE137F I51AE155F I51AE175F I51AE211F I51AE215F I51AE222F
Rated power kW 0.37 0.55 0.75 1.1 1.5 2.2
Mains voltage range 3/PE AC 340 V ... 528 V, 45 Hz ... 65 Hz
Output voltage 3 AC 0 V … 400 V
Rated mains current
without mains choke A 1.8 2.5 3.3 4.4 5.4 7.8
with mains choke A 1.4 2 2.6 3 3.7 5.3
Apparent output power kVA 0.9 1.2 1.6 2.2 2.6 3.8
Output current
2 kHz A - 1.8 2.4 3.2 3.9 5.6
4 kHz A 1.3 1.8 2.4 3.2 3.9 5.6
8 kHz A 1.3 1.8 2.4 3.2 3.9 5.6
16 kHz A 0.9 1.2 1.6 2.1 2.6 3.7
Weight kg 0.75 0.95 1.35