Conguraon of the restart behaviour aer a fault.
The sengs have no impact on errors and warnings of the inverter.
Parameter Name / value range / [default seng] Info
0x2839:002
(P760.02)
Fault conguraon: Restart delay
(Fault cong.: Restart delay)
0.0 ... [3.0] ... 1000.0 s
If a fault occurs, a restart is possible at the earliest aer the me set
here has elapsed.
0x2839:003
(P760.03)
Fault conguraon: Number of restart aempts
(Fault cong.: Restart counter)
0 ... [5] ... 255
Number of restart aempts aer a fault.
255 = unlimited number of restart aempts.
0x2839:004
(P760.04)
Fault conguraon: Trouble counter reset me
(Fault cong.: Tro.count r.me)
0.1 ... [40.0] ... 3600.0 s
Time of trouble-free operaon aer the expiry of which the fault coun-
ter is decreased by 1.
0x2839:005
(P760.05)
Fault conguraon: Trouble counter
(Fault cong.: Trouble counter)
Read only
Display of the current fault counter content.
The counter content is increased by 1 aer each restart aempt.
Related topics
4Error handling ^ 90
4Timeout für fault reacon ^ 311
Addional funcons
Automac restart
312