Parameter Name / value range / [default seng] Info
0x4046
(P755.00)
Acvaon of parameter set
(PSet acvaon)
Selecon of the acvaon method for the parameter change-over.
•
If the selecon is changed from "Via command... [0]/[1]" to "If the
selecon is changed...[2]/[3]" aer switch-on, the parameter set
selected via the funcons "Select parameter set (bit 0)" and "Select
parameter set (bit 1)" is acvated immediately. In case of selecon
[2], however, this only takes place if the inverter is disabled, the motor
is stopped or an error is acve.
0 Via command (disable required) The parameter set selected via the funcons "Select parameter set (bit
0)" and "Select parameter set (bit 1)" is acvated if the trigger assigned
to the "Load parameter set" funcon in 0x2631:040 (P400.40) provides a
FALSE-TRUE edge AND the inverter is inhibited, the motor is stopped or
an error is acve.
1 Via command (immediately) The parameter set selected via the funcons "Select parameter set (bit
0)" and "Select parameter set (bit 1)" is immediately acvated if the trig-
ger assigned to the "Load parameter set" funcon in 0x2631:040
(P400.40) provides a FALSE-TRUE edge.
2 If the selecon is changed (disable required) The parameter set selected via the funcons "Select parameter set (bit
0)" and "Select parameter set (bit 1)" is acvated if the state of these
selecon bits changes AND the inverter is inhibited, the motor is stop-
ped or an error is acve.
3 If the selecon is changed (immediately) The parameter set selected via the funcons "Select parameter set (bit
0)" and "Select parameter set (bit 1)" is acvated immediately if the
state of these selecon bits is changed.
Flexible I/O conguraon
Funcons for parameter change-over