Parameter Name / value range / [default seng] Info
0x4046
(P755.00)
Acvaon of parameter set
(PSet acvaon)
Selecon of the acvaon method for the parameter change-over.
If the selecon is changed from "Via command... [0]/[1]" to "If the
selecon is changed...[2]/[3]" aer switch-on, the parameter set
selected via the funcons "Select parameter set (bit 0)" and "Select
parameter set (bit 1)" is acvated immediately. In case of selecon
[2], however, this only takes place if the inverter is disabled, the motor
is stopped or an error is acve.
0 Via command (disable required) The parameter set selected via the funcons "Select parameter set (bit
0)" and "Select parameter set (bit 1)" is acvated if the trigger assigned
to the "Load parameter set" funcon in 0x2631:040 (P400.40) provides a
FALSE-TRUE edge AND the inverter is inhibited, the motor is stopped or
an error is acve.
1 Via command (immediately) The parameter set selected via the funcons "Select parameter set (bit
0)" and "Select parameter set (bit 1)" is immediately acvated if the trig-
ger assigned to the "Load parameter set" funcon in 0x2631:040
(P400.40) provides a FALSE-TRUE edge.
2 If the selecon is changed (disable required) The parameter set selected via the funcons "Select parameter set (bit
0)" and "Select parameter set (bit 1)" is acvated if the state of these
selecon bits changes AND the inverter is inhibited, the motor is stop-
ped or an error is acve.
3 If the selecon is changed (immediately) The parameter set selected via the funcons "Select parameter set (bit
0)" and "Select parameter set (bit 1)" is acvated immediately if the
state of these selecon bits is changed.
Flexible I/O conguraon
Funcons for parameter change-over
394