65305 0xFF19 Motor parameter idencaon error Keypad display: Motor ID fault
Cause Error type/response Remedy
During the automac idencaon of the
motor, an error has occurred.
Fault
Set motor data so that they comply with the
data on the motor nameplate.
Check wiring of the motor.
65335 0xFF37 Automac start disabled Keypad display: Auto start disab
Cause Error type/response Remedy
At mains connecon, a start command was
already available and the automac start at
power-up is set in 0x2838:002 (P203.02) to "O
[0]".
Fault Deacvate start command and reset error.
65366 0xFF56 Maximum motor frequency reached Keypad display: Max. motor freq.
Cause Error type/response Remedy
The maximum motor speed set in 0x6080
(P322.00) is acve.
The maximum output frequency of the inver-
ter has been reached.
Warning Check applicaon.
65413 0xFF85 Keypad full control acve Keypad display: Keypad full ctrl
Cause Error type/response Remedy
If the "Keypad Full Control" control mode is
acve.
Warning
Both the acvity of controlling and the set-
point selecon are carried out via the key-
pad.
Clicking the CTRL keypad key stops the control
mode again.
Related topics
4Keypad - Conguraon of R/F and CTRL buons ^ 254
Appendix
Error codes
453