Motor
connecon
A good shield connecon and short cable lengths reduce possible interferences caused by
problems with the EMC.
Example for preparing the EMC-compliant wiring or the motor cable
Fig. 8: Shield connecon
① Braid
②
large surface contacng of the braid
③ Heat-shrinkable tube
l maximally 500 mm
Switching in the motor cable
Switching on the motor side of the inverter is permissible:
F
or safety shutdown (emergency stop).
In case several motors are driven by one inverter (only in V/f operang mode).
Please note the following:
The switching elements on the motor side must be dimensioned for with the
maximum occurring load.
Connecon of motor temperature monitoring
If the terminal X109 is used, e. g. to connect an external PTC thermistor (PTC) or
a thermal c
ontact, ensure at least one basic insulaon to the potenals of
motor, mains and control terminals to not restrict the protecve separaon of
the control terminals.
Mounng/
installaon
Electrical installaon
Motor connecon
127