Inverter i550-C5.5/400-3 i550-C7.5/400-3 i550-C11/400-3 i550-C15/400-3
Rated power kW 5.5 7.5 11 15
Mains voltage range 3/PE AC 340 V ... 528 V, 45 Hz ... 65 Hz
Rated mains current
without mains choke A 14.3 16.6 23.7 32.3
with mains choke A 10.3 13.1 18.6 24
Apparent output power kVA 8.7 11 16 22
Output current
2 kHz A 11 14 21 27
4 kHz A 11 14 21 27
8 kHz A 11 14 21 27
16 kHz A 7.3 9.3 14 18
Power loss
4 kHz W 145 185 260 360
8 kHz W 190 240 340 460
at controller inhibit W 6 6 6 18
Overcurrent cycle 180 s
Max. output current A 16.5 21 31.5 40.5
Overload
me s 60 60 60 60
Recovery me s 120 120 120 120
Max. output current during the
recovery me
A
8.3 10.5 15.8 20.3
Overcurrent cycle 15 s
Max. output current A 22 28 42 54
Overload me s 3 3 3 3
Recovery me s 12 12 12 12
Max. output current during the
recovery me
A
8.3 10.5 15.8 20.3
Brake chopper
Max. output current A 16.6 29 29 43
Min. brake resistance Ω 47 27 27 18
Max. motor cable length shielded
without EMC category m 50 100
Category C1 (2 kHz, 4 kHz, 8 kHz) m -
Category C2 m 20
Weight kg 2.3 3.7 10.3
Technical data
3-phase mains connecon 480 V
Ra
ted data
61