Electrical installation
Common control terminals
Connection of relay output
6
222
EDS84ASC552 EN 10.0
Note!
ƒ Switching of control signals:
Use shielded cables
HF-shield termination by PE connection
The minimum load for a correct through-connection of the relay contacts
is 10 V DC and 10 mA. Both values must be exceeded at the same time.
ƒ Use shielded cables for switching the control signals and establish the
HF-shield termination through a PE connection.
ƒ For the switching operation of mains potentials, shielded cables are
sufficient.
ƒ To protect the relay contacts, use a c orresponding suppressor circuit in case
of an inductive or capacitive load!
ƒ The service life of the relay depends on the load type (ohmic, inductive, or
capacitive) and the height of capacity to be switched.
Note!
The following notes are described in detail in the software manual ”Parameter
setting”inthesection”I/Oterminals,”Relayoutput:
ƒ Use code C00118 to define the relay switching status.
ƒ The minimum period for a valid HIGH or LOW signal to c ontrol the relay can
be defined via the codes C00423/3 and C00423/4.