Technical data
Rated data
Operation with increased power at a 230 V mains
4
54
EDS84ASC552 EN 10.0
4.2.5 Operation with increased power at a 230 V mains
With an increased continuous power, the inverter can be connected to a next higher and
more powerful motor. The overload capacity according to operation with rated data
continues to exist. The drive of units with quadratic load characteristic as provided by
pumps o r fans are typical applications.
Note!
Operation with increased power is only permitted ...
ƒ With the rated data provided for the controller.
ƒ In the stated mains voltage range.
ƒ At switching frequencies of 2 kHz and 4 kHz.
ƒ At a max. ambient temperature of 40 °C.
ƒ With the stated installation types.
ƒ With the fuses, cable cross-sections, mains chokes and filters required for
this type of operation.
ƒ After parameterisation acc. to specification (cp. software manual
EDS84AV...)
Basis of the data
Mains Voltage Voltage range Frequency range
U
Lrated
[V] U
Lrated
[V] f[Hz]
1/N/PE AC 230 180-0%...264+0% 45-0%...65+0%
Mains current at I
aN
Apparent output power Motor power
with external
mains choke
without external
mains choke
U, V, W 4pol.ASM
Type I
LR
[A] I
LR
[A] S
aR
[kVA] P
aR
[kW]
E84AVxxx2512 3.6 4.1 0.8 0.37
E84AVxxx3712 5.0 - 1.0 0.55
E84AVxxx5512 6.0 6.4 1.3 0.75
E84AVxxx7512 8.4 - 1.7 1.1
E84AVxxx1122 11.9 14.4 2.4 1.5
E84AVxxx1522 13.7 - 3.0 2.2
E84AVxxx2222 - - - -