Electrical installation
Important notes
6
153
EDS84ASC552 EN 10.0
6 Electrical installation
6.1 Important notes
Danger!
Hazardous electrical voltage
Depending on the device, all power connections remain live up to 3 minutes
after the mains has been switched off.
Possible consequences:
ƒ Death or severe injuries when touching the power terminals.
Protective measures:
ƒ Wait for at least 3 minutes before working on the power terminals.
ƒ Make sure that all power terminals are deenergised.
Danger!
Dangerous voltage
The l eakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ Death or severe injuries when the device i s touched in the event of a fault.
Protective measures:
ƒ Implement the actions required in the EN 61800-5-1. Especially:
Fixed installation
PE connection must conform to standards (PE conductor diameter
10 mm
2
or PE conductor must be connected twice)