20
MultiSITE MS8000 Series Room Controllers
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp.
1/2 ZigBee Network
COM address 254
Node type
PAN ID 25
Channel 15
Network status No NWK
Permit join Off
Router
Table 4: ZigBee Network 1 / 2 Parameter Details.
Conguration Parameters
Default Value
Signicance and Adjustments
COM Address
Default Value: 254
Controller networking address. For wireless models, the use of the COM address is not mandatory. The COM
address is an optional way to identify a device on the network and is recommended if used with an MPM. It is
Mandatory for BACnet.
Range: 0 to 254
Node Type
Default: Router
Sets device to act as Router or Coordinator in a network.
Coordinator: Creates the network and manages the binding of wireless devices.
Router: Joins a network created by a coordinator (permit join must be set to “ON”).
Choices: Coordinator or Router
Pan ID (ZigBee Pan ID)
Default Value: 0
Personal Area Network Identification that links specific Controllers to specific ZigBee coordinators. For every
Controller reporting to a coordinator, set the SAME PAN ID value both on the coordinator and the Controller.
• The default value of 0 is NOT a valid PAN ID.
• For Controllers running Firmware version 1.3 and earlier, the PAN ID must be set to 501-1000 for the Controller
to act as a coordinator.
Range: 1 to 32767
Channel (ZigBee
Channel)
Default Value: 10
The frequency or channel on which the ZigBee network transmits and receives data. The channel of the Coordi-
nator must match that of the routers to exchange data.
The default value of 10 is NOT a valid channel. The valid range of available channel is from 11 to 25.
Using channels 15 and 25 is recommended.
Range: 10 to 25
Network Status (ZigBee
Network Status) Read
Only
Shows the current status of the ZigBee network.
No NWK: ZigBee configured but no network joined
Joined: ZigBee network joined
Online: Communicating (Exchanging data)
Display Readings: No NWK, Joined, Online
Permit Join
Default Value: On
Changing this value to “Off” on the Coordinator prevents any new ZigBee devices from joining the network.
Permit join can be On/Off when the Controller is a Coordinator, however the parameter is read only when the
Controller is a router. If not set to off manually the Permit join will stay On for 3 hours.
Choices: On or Off
ZigBee Network 1 / 2
When setting up a ZigBee network to bind with multiple devices, there must first be a Coordi-
nator to manage the initial binding between the Router and the end devices. After successful
binding, the Router becomes the parent to the end devices.
Before binding any ZigBee devices, the network must rst be created by the Coordinator..
NETWORK SCREENS
ZigBee Network 1 / 2
Figure 15: ZigBee Network 1 / 2 Display.
For MS8350 and MS8650