if ME.BV1==1 then
ME.BO98=1
delay=60
Body of the LUA Script
Title of LUA Script
Table 71: LUA Settings Parameter Details.
Conguration Parameters Default Value Signicance and Adjustments
Program cmd (Program Command)
Default Value: Run
Run: LUA script activated and runs continuously until deactivated
Stop: LUA script deactivated
Choices: Stop or Run
Program Status (Program Status)
Default Value: Idle
Read Only
Running: LUA script active
Halted: LUA script stopped and not active
Idle: LUA script is running but not currently performing any actions
Waiting: LUA script running and waiting for a response
Uploading: LUA script currently unloading from the Room Controller
Loading: LUA script currently loading to the Room Controller
Display Readings: Idle, Loading, Running, Waiting, Halted, Unloading
Program Error
Default Value: No error
Read Only
No error: No errors in LUA script
Syntax: Syntax error in LUA script detected
Runtime: Runtime error occurred while running LUA script
Memory: Device has run out of memory for the script
Display Readings No error, Syntax, Runtime, Memory
LUA Settings
The LUA settings screens show information about any custom LUA script uploaded to the Room Controller. LUA scripts are not program-
mable on the Room Controllers. LUA scripts can be uploaded to the Room Controller via the Uploader Tool or via BACnet.
LUA SCREENS
LUA Settings 1 / 3 and 2 / 3
Figure 84: LUA Settings 1 / 3 and 2 / 3 Displays.
For MS8350 and MS8650