CONFIGURATION SCREENS
MS8650 Conguration 1 / 11
MS8650 Configuration 1 / 11
Figure 33: MS8650 Conguration 1 / 11 Display.
For MS8650 Only
Table 25: MS8650 Conguration 1 / 11 Parameter Details.
Conguration Parameters Default Value Signicance and Adjustments
UI16 Config (Universal Input Configuration
No. 1)
Default Value: None
None: No function will be associated with the input. Input can be used for remote network
monitoring.
Rem NSB: Remote night setback (NSB) timer clock input. The scheduling gets set as per
the binary input and provides low cost setback operation via a dry contact.
Motion NO and Motion NC: Advanced PIR occupancy functions using a Normally Open
(NO) or Normally Closed (NC) remote PIR motion sensor.
Window: Forces system to disable any current heating or cooling action by Room Control-
ler when window is open.
Fan lock: When (G) Fan output is activated, if this input is not activated after 10 seconds,
the Room Controller disables Heat and Cool outputs and display “Fan Lock” alarm.
Open contact = No airflow alarm
Closed contact = Airflow present, normal operation
Choices: None, Rem NSB, Motion NO, Motion NC, Window and Fan lock
UI17 Config (Universal Input Configuration
No. 2)
Default Value: None
None: No function associated with input.
Door Dry: Room Controller goes to standby mode when door is opened then closed fol-
lowed by no presence detection for the next 10 seconds if the local PIR is used in this
application. The “Occupancy command” must be set to “Local Occupancy” and “Occupancy
Source” must be set to “Motion”.
Override: A closed contact forces the Room Controller to go in occupied mode. An open
contact keeps the current occupancy mode.
Filter: Backlit flashing filter alarm shows on the Room Controller screen when input is
energized.
Service: Backlit flashing Service alarm shows on Room Controller screen when input is
energized.
Choices: None, Door Dry, Override, Filter and Service.