Table 12: MS8350 Conguration 1 / 9 Parameter Details.
Conguration Parameters Default Value Signicance and Adjustments
UI16 Config (Universal Input Configuration
No. 1)
Default Value: None
None: No function will be associated with the input. Input can be used for remote network
monitoring.
Rem NSB: Remote night setback (NSB) timer clock input. The scheduling gets set as per
the binary input and provides low cost setback operation via a dry contact.
Motion NO and Motion NC: Advanced PIR occupancy functions using a Normally Open
(NO) or Normally Closed (NC) remote PIR motion sensor.
Window: Forces system to disable any current heating or cooling action by Controller when
window is open.
Fan lock: When (G) Fan output is activated, if this input is not activated after 10 seconds,
the Controller disables Heat and Cool outputs and display “Fan Lock” alarm.
Open contact = No airflow alarm.
Closed contact = Airflow present, normal operation.
Choices: None, Rem NSB, Motion NO, Motion NC, Window and Fan lock.
UI17 Config (Universal Input Configuration
No. 2)
Default Value: None
None: No function associated with input.
Door Dry: Controller goes to standby mode when door is opened then closed followed by
no presence detection for the next 10 seconds if the local PIR is used in this application.
The “Occupancy command” must be set to “Local Occupancy” and “Occupancy Source”
must be set to “Motion”.
Override: A closed contact forces the Controller to go in occupied mode. An open contact
keeps the current occupancy mode.
Filter: backlit flashing filter alarm shows on the Controller screen when input is energized.
Service: backlit flashing Service alarm shows on Controller screen when input is ener-
gized.
Choices: None, Door Dry, Override, Filter and Service.
1/9 Configuration
UI16 config None
UI17 config None
UI19 config None
Occupancy src Motion
Smart recovery Off
Setpoint func. Attach SP
MS8350 Configuration 1 / 9
CONFIGURATION SCREENS
MS8350 Conguration 1 / 9
Figure 24: MS8350 Conguration 1 / 9 Display.
For MS8350 Only