MS8350 Service View Screens
The service view screens show the current status of certain points locally on the Room Controller. These points can also be viewed through
the network. Service view values are Read Only values but allow a service contractor to visualize the status of key functionality to correctly
diagnose operational system issues.
Table 48: MS8350 Service View Screen 1 / 8 Parameter Details.
Conguration Parameters Default Value Signicance and Adjustments
Firmware Rev. (Firmware Revision)
Read Only
Shows Firmware version currently installed on the Room Controller. Upgrading to a newer
Firmware version deletes the previous Firmware version, however it is possible to set the
Controller to an earlier Firmware version with the Uploader Tool.
Room Temp. (Room Temperature)
Read Only
Shows the current room temperature. The user can set one of the following temperature
inputs to act as the source for the room temperature’s present value:
Wired: Sensor across UI20 (RS) and common
Internal: Controller’s internal temperature sensor
WL 1 to WL 10: Wireless ZigBee end devices
Display Readings: Wired, Internal, WL1 to WL10
UI19 changeover (Universal Input
Changeover Sensor)
Read Only
Shows the changeover sensor connected to UI20 (RS) terminal.
UI20 Temp (Room Temperature Sensor)
Read Only
Shows the temperature of the sensor connected to UI20 (RS) terminal.
Outdoor Temp. (Outdoor Temperature)
Read Only
Shows the outdoor temperature on the main screen.
Room Humidity
Read Only
Shows percentage of humidity in room from selected local or wireless devices. Refer to
RH sensor parameter to select RH source.
Display Readings: %RH
SERVICE VIEW SCREENS
MS8350 Service View Screen 1 / 8
MS8350 Service View Screen 1 / 8
Figure 50: MS8350 Service View Screen 1 / 8.
For MS8350 Only