95
User Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp.
6/7 Configuration
Language English
Units °C
Low backlight 60 %
Night backlight 5 %
RH display Disable
Temperature
Enable
Hysteresis
Threshold
On
XX °F
XX °F
Table 69: Temperature Alarm Conguration Parameter Details.
Conguration Parameters Default Value Signicance and Adjustments
Enable (Temperature Alarm Enabled)
Default Value: Off
Enables wireless device to alert the Room Controller if temperature value reaches defined
value in a particular.
Choices: On or Off
Threshold (Temperature Alarm Threshold)
Default Value: 40 °F (4.5 °C)
Sets alarm threshold for system temperature sensors.
Range: 32° to 45°F (0° to 7°C)
Hysteresis (Temperature Alarm Hysteresis)
Default Value: 4°F (2°C)
Choices: 0° to 10°F (0° to 5.5°C)
Temperature Alarm Configuration
This screen is a subset of the Ecosystems screen and triggers an alarm only for the Water sensors with temperature measurement.
WIRELESS SCREENS
Temperature Alarm Conguration
Figure 82: Temperature Alarm Conguration Display.
For MS8350 and MS8650

Related product manuals