MultiSITE MS8000 Series Room Controllers
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp.
SETPOINTS SCREENS
MS8650 Setpoints 2 / 2
MS8650 Setpoints 2 / 2
Figure 47: MS8650 Setpoints 2 / 2 Display.
For MS8650 Only
2/2 Setpoints
Max. heating
Min. deadband
Default heat
3.0 °F
90.0 °F
54.0 °F
55.0 °F
72.0 °F
Min. cooling
Supply air SP
50 %RH
Dehum. SP
Table 45: MS8650 Setpoints 2 / 2 Parameter Details.
Conguration Parameters Default Value Signicance and Adjustments
Default Heat (Default Heating Setpoint)
Default Value: 72°F (22°C)
Used for hospitality applications in stand-alone mode only to reset the occupied setpoints
when a new guest enters the room.
When the Room Controller is in unoccupied mode, any movement detected by a wired,
wireless or local PIR sensor changes the occupancy mode to occupied modes and uses
the “Default Heating Setpoint” as the new occupied setpoints.
This functionality is only valid when Stand-by mode = Offset and “Setpoint Func” is set to “At-
tached”.
Range: 65 to 80°F (18.5 to 26.5°C)
Min. Deadband (Minimum Deadband)
Default Value: 3°F (1.5°C)
Temperature offset between the Cooling and Heating setpoints to ensure that Cooling
setpoint is always warmer than the Heating setpoint.
Cooling setpoint (Heating setpoint + Deadband)
Range: 2 to 5°F (1.0 to 2.5°C)
Max. Heating (Heating Setpoint Limit)
Default Value: 90°F (32°C)
Maximum Occupied, Unoccupied, Standby and Override Heating setpoints maximum limit.
Range: 40 to 90°F (4.5 to 32.0°C)
Min. Cooling (Cooling Setpoint Limit)
Default Value: 54°F (12°C)
Maximum Occupied, Unoccupied, Standby and Override Cooling setpoint adjustment.
Range: 54 to 100°F (12.0 to 37.5°C)
Supply Air SP (Supply Air Setpoint)
Default Value: 55°F (12°C)
Free cooling supply air setpoint when economizer mode is enabled.
Range: 50 to 90°F (10.0 to 32.0°C)
Dehum. SP (Dehumidification Setpoint)
Default Value: 50%RH
Used only if dehumidification sequence is enabled.
Range: 30 to 95%RH