SETPOINTS SCREENS
MS8650 Setpoints 1 / 2
MS8650 Setpoints 1 / 2
Figure 46: MS8650 Setpoints 1 / 2 Display.
For MS8650 Only
Table 44: MS8650 Setpoints 1 / 2 Parameter Details.
Conguration Parameters Default Value Signicance and Adjustments
Unocc. Cool (Unoccupied Cool Setpoint)
Default Value: 80°F (27°C)
Cooling Temperature setpoint used by the Room Controller when in Unoccupied mode.
Range: 54 to 100°F (12.0 to 37.5°C)
Standby Cool (Standby Cool Setpoint)
Default Value: 78°F (25.5°C)
Cooling Temperature setpoint used by the Room Controller when in Standby mode.
Range: 54 to 100°F (12.0 to 37.5°C)
Occ. Cool (Occupied Cool Setpoint)
Default Value: 75°F (24°C)
Cooling Temperature setpoint used by the Room Controller when in Occupied or Override
mode.
Range: 54 to 100°F (12.0 to 37.5°C)
Occ. Heat (Occupied Heat Setpoint)
Default Value: 72°F (22°C)
Heating Temperature setpoint used by the Room Controller when in Occupied mode.
Range: 40 to 90°F (4.5 to 32.0°C)
Standby Heat (Standby Heat Setpoint)
Default Value: 69°F (20.5°C)
Heating Temperature setpoint used by the Room Controller when in Standby mode.
Range: 40 to 90°F (4.5 to 32.0°C)
Unocc. Heat (Unoccupied Heat Setpoint)
Default Value: 62°F (17°C)
Heating Temperature setpoint used by the Room Controller when in Unoccupied or Over-
ride mode.
Range: 40 to 90°F (4.5 to 32.0°C)