BACnet Network Settings
BACnet network screen shows when BACnet is selected in wired protocol parameter.
Table 6: BACnet Network Parameter Details.
Conguration Parameters Default Value Signicance and Adjustments
Comm address
Default value: 254
Controller networking address.
Default value of 254 disables BACnet communication for the Controller.
Range: 0 to 254
Network Units (Measurement Units)
Default Value: SI
Network units transmitted over the BACnet network.
Use the Temperature scale parameter to change the display units locally on the Controller.
Imperial: Network units shown as Imperial units.
SI: Network units shown as International Metric units.
Choices: Imperial or SI
Network Language
Default Value: English
Network Language
Network language/object names transmitted over network.
Choices: English, French or Spanish
Baud Rate (BACnet Baud Rate)
Default Value: Auto
Leave the value at Auto unless instructed otherwise as this automatically detects BACnet
baud rate.
Choices: Auto, 115200, 76800, 57600, 38400, 19200, and 9600
BACnet Status
Read Only
BACnet Status
Read Only value shows if a BACnet Network is detected or not.
Display Readings: Online or Offline
NETWORK SCREENS
BACnet Network Settings
Figure 17: BACnet Network Display.
For MS8350 and MS8650