MultiSITE MS8000 Series Room Controllers
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp.
Conguration Parameters Default Value Signicance and Adjustments
UI19 Config (Universal Input Configuration
No. 3)
Default Value: None
None: No function associated with input though input can be used for remote network
monitoring.
COC/NH: change over dry contact normally heat. Used for hot/cold water or air change
over switching in 2-pipe systems.
COC/NC: change over dry contact normally cool. Used for hot/cold water or air change
over switching in 2-pipe systems.
COS: change over sensor. Used for hot/cold water or air changeover switching in 2 pipe
systems.
Choices: None, COC/NH, COC/NC and COS.
Occupancy src (Occupancy Source)
Default Value: Motion
Motion: Occupancy status received from motion sensor.
Schedule: Occupancy status determined by the schedule.
Choices: Motion and Schedule.
Smart Recovery (Enable Smart Recovery)
Default Value: Off
Off: No smart recovery. The occupied schedule time is the time at which the system will
restart.
On: Smart recovery active. The occupied schedule time is the time at which the desired
occupied temperature will be attained. The Controller automatically optimizes the equip-
ment start time. In any case, the latest a system will restart is 10 minutes prior to the
occupied period time.
Smart recovery is automatically disabled if BI16 is configured to remote NSB.
Choices: Off or On.
Setpoint Func. (Setpoint Function)
Default Value: Dual SP
Local setpoint settings to set the local setpoint interface for the User.
Dual SP: “Minimum” Deadband, Heat and Cool Setpoints can be adjusted independently.
Attach SP: “Fixed” Deadband, Heat and Cool setpoints always follow each other, sepa-
rated by Deadband value (acts like a single setpoint).
Choices: Dual SP or Attach SP.
Table 13: MS8350 Conguration 1 / 9 Parameter Details, continued.
CONFIGURATION SCREENS
MS8350 Conguration 1 / 9