36
MultiSITE MS8000 Series Room Controllers
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp.
Conguration Parameters Default Value Signicance and Adjustments
BO8 Aux. Config (BO8 Aux Output
Configuration)
Default Value: Reheat
Aux contact function used for reheat if sequence is set to use BO8 for reheat through
network or local. Output directly follows occupancy of Controller.
Reheat: reheat through network or local
Aux NO: Occ or St-By = Contact Closed / Unoccupied = Contact Opened
Aux NC: Occ or St-By = Contact Opened / Unoccupied = Contact Closed. Output to follow
directly main occupancy and Fan on command. Typically used for 2 position fresh air
damper applications.
Aux F&NO: Occ or St-By & Fan On = Contact Closed/Unoccupied and Fan On or Off =
Contact Opened
Aux NC: Occ or St-By & Fan On = Contact Opened/Unoccupied and Fan On or Off =
Contact Closed
Choices: Reheat, Aux NO, Aux NC, Aux F&NO and Aux F&NC
Floating Time (Floating Actuator Timing)
Default Value: 1.5 minutes
Floating actuator stroke timing value. Maximum stroke time of floating valve actuator.
Range: 0.5 to 9.0 minutes (0.5 minute increments)
Action
Default Value: DA
Direct Acting and Reverse Acting
For Analog Heating signals. Reverse Acting or Direct Acting signal for Analog Output
signals.
DA = 0 to 100% = 0 to 10 Vdc
RA = 0 to 100% = 10 to 0 Vdc
Choices: DA or RA
Table 19: MS8350 Conguration 5 / 9 Parameter Details, continued.
CONFIGURATION SCREENS
MS8350 Conguration 5 / 9
For MS8350 Only