CONFIGURATION SCREENS
MS8650 Conguration 5 / 11
For MS8650 Only
MS8650 Configuration 5 / 11
Figure 37: MS8650 Conguration 5 / 11 Display.
Table 32: MS8650 Conguration 5 / 11 Parameter Details.
Conguration Parameters Default Value Signicance and Adjustments
Prop. Band (Proportional Band
Setting)
Default Value: 3
Adjusts proportional band used by Room Controller PI control loop.
Default value of 3 gives satisfactory operation in most normal installation cases. The use of a superior
proportional band different than the factory value is normally warranted in applications where Room
Controller location is problematic and leads to unwanted cycling of the unit. A typical example is a wall
mounted Room Controller installed between return and supply air feeds and is directly inuenced by
the supply air stream of unit.
Range: 3 to 10
Value
Effective Proportional Band
Fahrenheit Celsius
3 3 1.2
4 4 1.7
5 5 2.2
6 6 2.8
7 7 3.3
8 8 3.9
9 9 5.0
10 10 5.6
Heat Stages (Number of Heating
Stages)
Default Value: 2 stages
Sets number of Heating Stages applicable to 2 stage models only.
0 Stages: Only (UO11) modulating 0-10 Vdc output is used for Heating. W1 and W2 are dis-
abled.
1 Stage: Only W1 (BO8) terminal is used. W2 is disabled.
2 Stages: Both W1 (BO8) and W2 (UO9) terminals are used in sequence.
Choices: 0, 1 or 2 stages