Conguration Parameters Default Value Signicance and Adjustments
Calib. Temp. (Calibration Room
Temperature Sensor)
Default Value: 0°F
Room temperature sensor calibration. Offset can be added or subtracted to actual dis-
played room temperature.
Range: ±5.0°F (±2.5°C)
Calib. OS Temp. (Calibration Outside
Temperature Sensor)
Default Value: 0°F
Outside air temperature sensor calibration. Offset that can be added or subtracted to the
actual displayed outdoor temperature.
Range: ±5.0°F (±2.5°C)
Calib. Humid. (Calibrate Humidity Sensor)
Default Value: 0.0%RH
Offset that can be added or subtracted to actual displayed humidity.
Range: ±15.0%RH
RH Sensor (Relative Humidity Sensor)
Default Value: Internal
Sets the source of the indoor room humidity. This parameter allows the user to designate
either the Room Controller (only models supporting humidity) or any of the bound wireless
devices that support humidity to act as the source for the room humidity.
Internal: Sets the Room Controller as the source for the room humidity.
WL 1 to WL 10: Sets the selected wireless ZigBee PRO device as the source for the room
humidity. Only one device can be selected.
Choices: None, Internal, WL1 to WL10
Calib. humid. conguration is only for models with humidity sensor.