9. Basic functions
9-13
SV-iC5
Accel/Decel pattern setting
Group LED display Parameter name
Min/Max
range
Set value Unit
Function
group 1
F 2 [Accel pattern] 0 Linear
0
F 3 [Decel pattern] 1 S-curve
H17
S-Curve accel/decel start
side
1~100
40 %
H18
S-Curve accel/decel end
side
40 %
Accel/Decel pattern is settable at F2 and F3.
Linear : This is a general pattern for constant torque applications
S-curve : This curve allows the motor to accelerate and decelerate smoothly.
Appropriate applications: Elevator door, lifts..
Caution :
For S-curve, the actual Accel/Decel time takes longer than the time set by user.
Run
command
Freq.
Accel time Decel time
Freq
H17
H17 H18 H18
Accel/Decel
Ref. Freq.
Accel
Starting
Accel
Ending
Decel
Starting
Decel
Ending
1/2 of
Accel/Decel Ref.
Freq