EasyManuals Logo

LSIS S100 Series User Manual

LSIS S100 Series
95 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #34 background imageLoading...
Page #34 background image
Chapter 5. Table of Functions
32
Code
Comm.
Address
Name
LCD
Display
Setting Range
Initial
value
Property*
V/F
SL
Ref.
5
I2
6
Int 485
8
FieldBus
12
Pulse
09
0h1109
Control mode
Control Mode
0
V/F
0: V/F
X/A
O
O
2
Slip
Compen
4
IM
Sensorless
10
0h110A
Torque Control
Torque Control
0
No
0: No
X/A
X
O
1
Yes
11
0h110B
Jog frequency
Jog Frequency
0.00, Start
frequency-
Maximum
frequency(Hz)
10.00
O/A
O
O
12
0h110C
Jog run
acceleration time
Jog Acc Time
0.0
-
600.0(s)
20.0
O/A
O
O
13
0h110D
Jog
run
deceleration
time
Jog Dec Time
0.0
-
600.0(s)
30.0
O/A
O
O
14
0h110E
Motor capacity
Motor Capacity
0: 0.2kW,
1: 0.4kW
2: 0.75kW,
3: 1.1kW
4: 1.5kW,
5: 2.2kW
6: 3.0kW,
7: 3.7kW
8: 4.0kW,
9: 5.5kW
10: 7.5kW,
11: 11.0kW
12: 15.0kW,
13: 18.5kW
14: 22.0kW,
15: 30.0kW
V
aries by
Motor
capacity
X/A
O
O
15
0h110F
Torque boost
options
Torque Boost
0
Manual
0: Manual
X/A
O
X
1
Auto
16
3
0h1110
Forward Torque
boost
Fwd Boost
0.0
-
15.0(%)
2.0
X/A
O
X
17
3
0h1111
Reverse Torque
boost
Rev Boost
0.0
-
15.0(%)
2.0
X/A
O
X
18
0h1112
Base frequency
Base Freq
30.00
-
400.00(Hz)
60.00
X/A
O
O
19
0h1113
Start frequency
Start Freq
0.01
-
10.00(Hz)
0.50
X/A
O
O
20
0h1114
Maximum
frequency
Max Freq
40.00
-
400.00(Hz)[V/F,
Slip Compen]
40.00-
60.00
X/A
O
O
3
Displayed when dr.15 is set to 0 (Manual)

Other manuals for LSIS S100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS S100 Series and is the answer not in the manual?

LSIS S100 Series Specifications

General IconGeneral
BrandLSIS
ModelS100 Series
CategoryController
LanguageEnglish

Related product manuals