Chapter 5. Table of Functions
39
Code
Address
Name LCD Display Setting Range
Value
Property*
V/F
SL
Ref.
03
12
0h1303
acceleration start
point gradient
Acc S Start 1-100(%) 40 X/A O O
04
12
0h1304
acceleration end
point gradient
Acc S End 1-100(%) 40 X/A O O
05
13
0h1305
deceleration start
point gradient
Dec S Start 1-100(%) 40 X/A O O
06
13
0h1306
deceleration end
point gradient
Dec S End 1-100(%) 40 X/A O O
07 0h1307
Start Mode Start Mode
0:Acc X/A O O
08 0h1308
Stop Mode Stop Mode
0:Dec X/A O O
4
Braking
09 0h1309
Selection of
prohibited
rotation direction
Run Prevent
0: None
X/A O O
10 0h130A
Starting with
power on
Power-on Run
0:No O/A O O
12
14
0h130C
at startup
DC-Start Time
0.00-60.00(s) 0.00 X/A O O
13 0h130D
applied DC
DC Inj Level 0-200(%) 50 X/A O O
14
15
0h130E
time before DC
braking
DC-Block Time
0.00- 60.00(s) 0.10 X/A O O
15
16
15
0h1310
DC braking rate
Level
0-200(%) 50 X/A O O
17
15
0h1311
frequency
DC-Brake Freq
60Hz
5.00 X/A O O
20 0h1314
Dwell frequency
on acceleration
Acc Dwell Freq
Maximum
frequency(Hz)
5.00 X/A O O
21 0h1315
time on
acceleration
Acc Dwell
Time
0.0-60.0(s) 0.0 X/A O O
12
Displayed when Ad. 01 is set to 1 (S-curve).
13
Displayed when Ad. 02 is set to 1 (S-curve).
14
Displayed when Ad. 07 is set to 1 (DC-Start).
15
Displayed when Ad. 08 is set to 1 (DC-Brake).