Chapter 5. Table of Functions
67
Code
Comm.
Address
Name LCD Display Setting Range
Initial
Value
Property*
V/F
SL
Ref.
81 0h1B51
Low voltage fault
decision delay time
LVT Delay 0.0-60.0(s) 0.0 X/A O O
82 0h1B52 LV2 Selection LV2 Enable
0 No
0 X/A O O
1 Yes
86 0h1B56
Accumulated
percent of fan
usage
Fan Time Perc 0.0~100.0[%] 0.0 -/A O O
87 0h1B57
Fan exchange
warning level
Fan Exchange
level
0.0~100.0[%] 90.0 O/A O O
88
56
0h1B58 Fan reset time Fan Time Rst
0 No
0 X/A O O
1 Yes
89 0h1B59 CAP, FAN Status CAP, FAN State
Bit
00~10
0 -/A O O
00
-
01
CAP Warning
10
FAN Warning
90
56
0h1B5A
Warning
information
- - - -/7 O O
91
56
0h1B5B Fault history 1 - - - -/7 O O
92
56
0h1B5C Fault history 2 - - - -/7 O O
93
56
0h1B5D Fault history 3 - - - -/7 O O
94
56
0h1B5E Fault history 4 - - - -/7 O O
95
56
0h1B5F Fault history 5 - - - -/7 O O
96
56
0h1B60
Fault history
deletion
-
0 No
0:No -/7 O O
1
Yes
56
Will not be displayed when an LCD keypad is in use.