Chapter 3 Installation and Test Operation
3-2
3.1.2 Operation steps
The steps for operating FEnet I/F module from installation to operation will be described below. After
the product installation is complete, install and configure the system to be operated as specified in the
following steps.
Operation Steps.
1) Install FEnet I/F module on the base
2) Connect FEnet I/F module with other network.
3) Turn the system power on
4) Run XG5000 to setup basic parameters.
5) After the basic parameters are downloaded, reset the module.
6) After the module reset, check if RUN and I/F RUN LEDs of the module are normal.
7) If LED and CPU are normal, check the status information of the communication module and CPU
with the diagnosis function of XG5000.
8) If the module status is normal, check if response comes in when PING test is executed through a
computer connected to the network if a computer is connected to the network. If computer is not
connected to the network, use the live check item among diagnosis services of XG5000 to check
the response.
9) Setup the communication services and download the setup items to the PLC with XG5000.
10) Enable communication service.
11) After programming with XG5000, write it on CPU to start the operation.
Notes
1) After station No. and IP address are specified through XG5000, surely reset the applicable
module. The first station No. and IP address (including frames) will keep the value read from the
communication module when initialized. Any changed details during communication will not be
applied during Run.