Chapter 6 High-speed Link Service
6-3
6.3 Operation Sequence through High-speed Link
Set basic parameters
1
Use XG5000
Select HS link
2
HS link setting window
Select HS link parameters
3
HS link 1~12
Set communication module
4
Module type
FEnet
5
Base No.(0~7)
6
Slot No.(0~11)
Set communication period
7
20ms~10s
Set HS link block (register list)
8
Station type
Master
9
Station No.(0~63)
10
Block type
Send or Receive
11
Block No.(0~31)
12
Read area/Save area
13
Size (1~200 words)
Online (after local-connected )
14
Write
HS link parameters
Set link enable
5
HS link1~12
Setup the parameters for
correspondent station as in 1~15
above.
Specify and download the basic parameters such
HS link station No., media, IP address, etc. Reset
the PLC to apply downloaded basic parameters.
Open HS link setting window of XG5000
Select HS link number.
(1 HS link number is available for 1
communication module)
1. Self-station No. for Send blocks (auto
Correspondent station No. for Receive blocks
2. Totally, 128 blocks are available. Send/Receive
data sorted out by station No. and block No. of
each other.
3. Self-stations area to read for Send, Self-
stations area to save the received data for
Receive
Download HS link parameters from XG5000 onto
CPU
Set link-enable for the applicable HS link number to
be started the HS link service with XG5000.
Select the networks Send period
(20ms~10s)
Input network type and base and slot No. where
communication module is installed.