13 - 10 Troubleshooting Millennium Systems Issue 5 June 2000
CTRL MIN Minor
Communication
Fail Alarm
Blinking
ALM LED
on rectifier
Loss of
communication
with controller:
•Defective
interface from
rectifier to
controller
•Internal
controller or
rectifier failure
1. Verify that the controller
is powered and operating
correctly.
2. If there are no controller
alarms, replace the
equipment that has lost
communication.
•If the problem is not
corrected, call your local
RTAC representative.
CTRL MIN Self Fail Test -- See “Controller
Fail”.
See “Controller Fail”.
CTRL MIN Thermal Probe
Failure
-- Battery thermal
probe has failed.
Call your local RTAC
representative.
Table 13-C: Controller Alarms
(See Figures 12-2 and 12-3)
Controller
LED
Controller
Alarm
Status
Millennium
Controller Display
Other
Indication(s)
Possible
Problem(s)
Possible Solution(s)